4 SACE Tmax Moulded-case circuit-breakers | ABB ABB | SACE Tmax Moulded-case circuit-breakers 5
Up to 250 A
Up to 1000 A
Up to 3200 A
A single family of moulded-case circuit-breakers up to 3200 A
Construction characteristics
SACE Tmax XT1 XT2 XT3 XT4
Size [A] 160 160 250 160/250
Rated service voltage, Ue (AC) 50-60Hz [V] 690 690 690 690
DC [V] 500 500 500 500
(4)
Versions Fixed, Plug-in
(1)
Fixed, Plug-in, Withdrawable Fixed, Plug-in Fixed, Plug-in, Withdrawable
Breaking capacity according to IEC 60947-2 B C N S H N S H L V N S N S L H V
Rated ultimate short-circuit breaking capacity, Icu
Icu @ 220-230-240V 50-60Hz (AC) [kA] 25 40 65 85 100 65 85 100 150 200 50 85 65 85 100 150 200
Icu @ 415V 50-60Hz (AC) [kA] 18 25 36 50 70 36 50 70 120 150 36 50 36 50 70 120 150
Icu @ 690V 50-60Hz (AC) [kA] 3 4 6 8 10 10 12 15 18 20 5 6 10 12 15 20 25/100
(2)
(DC) 500V - 2 poles in series [kA] - - - - - - - - - - - - 36 50 70 85 100
(DC) 500V - 3 poles in series [kA] 18
(3)
25
(3)
36
(3)
50
(3)
70
(3)
36 50 70 85 100 36 50 36 50 70 85 100
(DC) 750V - 3 poles in series [kA] - - - - - - - - - - - -
(4) (4) (4) (4) (4)
Rated service short-circuit breaking capacity, Ics
Ics @ 220-230-240V 50-60Hz (AC) [kA] 100% 100% 75%(50) 75% 75% 100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%
Ics @ 415V 50-60Hz (AC) [kA] 100% 100% 100% 75% 50% (37,5) 100% 100% 100% 100% 100% 75% 50% (27) 100% 100% 100% 100% 100%
Ics @ 690V 50-60Hz (AC) [kA] 100% 100% 100% 75% 50% 100% 100% 100% 75% (15) 75% (15) 75% 50% 100% 100% 100% 100% 75% (20)
Mechanical life [N° Operations] 25000 25000 25000 25000
[N° Hourly opertions] 240 240 240 240
Electrical life @ 415V (AC) [N° Operations] 8000 8000 8000 8000
[N° Hourly opertions] 120 120 120 120
Dimensions
(Width/Depth/Height)
3 poles [mm] 76,2x70x130 90x82,5x130 105x70x150 105x82,5x160
4 poles [mm] 101,6x70x130 120x82,5x130 140x70x150 140x82,5x160
(1)
XT1 plug-in In max=125A
(2)
25kA@690V available for XT4 250; 100kA@690V available
for XT4 160
(3)
XT1 500V DC 4 poles in series
(4)
XT4 750V DC ask ABB SACE whether available
(5)
Withdrawable not available for T6 1000A
(6)
V version only available for frame 630A/800A
(7)
75% for T5 630
(8)
50% for T5 630
(9)
Only for T7 800/1000/1250
(10)
Only for T7 800
SACE Tmax T4 T5 T6
Size [A] 320 400/630 630/800/1000
Rated service voltage, Ue (AC) 50-60Hz [V] 690 690 690
(DC) [V] 750 750 750
Versions Fixed, Plug-in, Withdrawable Fixed, Plug-in, Withdrawable Fixed, Withdrawable
(5)
Breaking capacity according to IEC 60947-2 N S H L V N S H L V N S H L V
(6)
Rated ultimate short-circuit breaking capacity, Icu
Icu @ 220-230-240V 50-60Hz (AC) [kA] 70 85 100 200 200 70 85 100 200 200 70 85 100 200 200
Icu @ 415V 50-60Hz (AC) [kA] 36 50 70 120 200 36 50 70 120 200 36 50 70 100 150
Icu @ 690V 50-60Hz (AC) [kA] 20 25 40 70 80 20 25 40 70 80 20 22 25 30 40
(DC) 500V - 2 poles in series [kA] 25 36 50 70 100 25 36 50 70 100 20 35 50 65 70
(DC) 500V - 3 poles in series [kA] – – – – – – – – – – – – – – -
(DC) 750V - 3 poles in series 16 25 36 50 70 16 25 36 50 70 16 20 36 50 50
Rated service short-circuit breaking capacity, Ics
Ics @ 220-230-240V 50-60Hz (AC) [kA] 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 100%
Ics @ 415V 50-60Hz (AC) [kA] 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 75%
Ics @ 690V 50-60Hz (AC) [kA] 100% 100% 100% 100% 100% 100% 100% 100%
(7)
100%
(8)
100%
(8)
75% 75% 75% 75% 75%
Mechanical life [N° Operations] 20000 20000 20000
[N° Hourly opertions] 240 120 120
Electrical life @ 415V (AC) [N° Operations] 6000 7000 (400 A) - 5000 (630 A) 7000 (630A) - 5000 (800A) - 4000 (1000A)
[N° Hourly opertions] 120 60 60
Dimensions
(Width/Depth/Height)
3 poles [mm] 105 x 103.5 x 205 140 x 103.5 x 205 210 x 103.5 x 268
4 poles [mm] 140 x 103.5 x 205 186 x 103.5 x 205 280 x 103.5 x 268
SACE Tmax T7 T8
Size [A] 800/1000/1250/1600 2000/2500/3200
Rated service voltage, Ue (AC) 50-60Hz [V] 690 690
(DC) [V] - –
Versions Fixed, Withdrawable Fixed
Breaking capacity according to IEC 60947-2 S H L V
(9)
X
(10)
L V
Rated ultimate short-circuit breaking capacity, Icu
Icu @ 220-230-240V 50-60Hz (AC) [kA] 85 100 200 200 170 85 130
Icu @ 415V 50-60Hz (AC) [kA] 50 70 120 150 170 85 130
Icu @ 690V 50-60Hz (AC) [kA] 30 42 50 60 75 50 80
(DC) 500V - 2 poles in series [kA] – – – – – – –
(DC) 500V - 3 poles in series [kA] – – – – – – –
(DC) 750V - 3 poles in series – – – – – – –
Rated service short-circuit breaking capacity, Ics
Ics @ 220-230-240V 50-60Hz (AC) [kA] 100% 100% 100% 100% 100% 100% 75%
Ics @ 415V 50-60Hz (AC) [kA] 100% 100% 100% 100% 100% 100% 75%
Ics @ 690V 50-60Hz (AC) [kA] 100% 75% 75% 75% 100% 100% 75%
Mechanical life [N° Operations] 10000 15000
[N° Hourly opertions] 60 60
Electrical life @ 415V (AC) [N° Operations] 2000 (versioni S, H, L) / 3000 (versione V) 4500(2000A);4000 (2500A);3000 (3200A)
[N° Hourly opertions] 60 20
Dimensions
(Width/Depth/Height)
3 poles [mm] 210 x 154 (leva) /178 (motorizzabile) x 268 427 x 282 x 382
4 poles [mm] 280 x 154 (leva) /178 (motorizzabile) x 268 553 x 282 x 382
Comentários a estes Manuais